From right side to left side, the first, second, third and fourth digit of AOP individually indicate the alarm output terminal of HIAL, LoAL, HdAL, and LdAL. 0 shows no output. 1, 2, 3 or 4 indicates alarm outputted to AL1, AL2, AU1 or AU2. For example,
AOP = 3 3 0 1
LoAL HdAL LoAL HIAL
It shows that HIAL is sent to AL1, LoAL has no output, HdAL and LdAL are sent to AU1. Note 1: When AUX is used as auxiliary output in bidirectional (heating/refrigerating) control, alarm to AU1 and Au2 won’t work.
Note 2: Installing L5 dual relay output module in ALM or AUX can implement AL2 or AU2 alarm.
Ans. PI Series -Create New Project >> select HMI Model and Angle >> ok.
LEVI Series- Create New Project >> Select HMI model as Model_TV (i.e. LEVI 2070_TV).
Ans. Open Download (If HMI is accessed, it will show [USB: Download] in [Download] menu) >> Recalibration >> Press + Sign until sound of beep. On HMI Press top left corner for 5 to 10 sec. >> Press + Sign until sound of beep.
Ans. Press top right corner of HMI for 5 to 10 sec >> System Screen >> System Setting >> Date/Time.
Ans. Open PLC program >> Select PLC in tools >> Select PLC type >> Select model of PLC >> Ok.
Ans. Make sure PLC supply is On >> Connect micro USB cable to PLC >> Select transfer setup >> Connection test >> PLC detect successfully >> Ok >> Select compile >> Successfully Compile Ok >> Select write to PLC >> Select param+prog >> Execute.
Ans. Make sure PLC supply is On >> Connect micro USB cable to PLC >> Select transfer setup >> Connection test >> PLC detect successfully >> ok >> Select read from PLC >> Select param+prog >> Execute.
Ans. Open PLC program >> switch the PLC from run to stop mode >> Select Encryption tools >> Select which type of password you wants to set .
We can set :
1.Program Password
2.Download Password
3.Upload Password
4.Clock Password
5.PLC Code.
Ans. First of all give supply to PLC >> Connect micro USB cable to PLC >> Select transfer setup >> Connection test >> PLC detect successfully >> ok >> switch the PLC from run to stop mode >> Select clear memory >> Select PLC memory >> Execute.
Ans. First of all give supply to PLC >> Connect micro USB cable to PLC >> Select transfer setup >> Connection test >> PLC detect successfully >> ok >> switch the PLC from run to stop mode >> Select clock setting >> Select read PC time >> Set time.
Ans. Open PLC program >> Select compile >> Ok >> Select generate download file >> Give path to save file >> Ok.
For download generated file.
Open wecon PLC editor >> Select open >> Select generated file >> Select write to PLC >> Select param+prog >> Execute.
Ans. Open PLC program >> Select compile >> Ok >> Select Udisk download file >> Give path to save file >> Ok.
On HMI Press top right corner for 5 to 10 sec >> System Screen >> Update project.
Ans. PI Series – Project >> Project Settings >> HMI Model >> Ok.
LEVI Series- Open Setting >> Project Properties >> General >> Device type >> HMI Model >> Ok.
Ans. PI Series -Project >> Communication >> New >> Set communication, serial Port & Device Type >> Ok.
LEVI Series- Open Setting >> Communication >> New >> Set port & Device Type >> Ok.
Ans. PI Series -Make Sure HMI supply is on >> Open HMI Program >> Project >> Compile >> Connect downloading cable >> Download (If HMI is accessed, it will show [USB: Download] in [Download] menu) >> PC to HMI. Download via Ethernet cable- Press top right corner of HMI Screen >> Network >> Set HMI IP >> Connect Ethernet Cable >> Select PC Port Ethernet >> Set IP of HMI >> PC to HMI.
LEVI Series- Make Sure HMI supply is on >> Open HMI Program >> Tool >> Compile >> Connect downloading cable >> Download (If HMI is accessed, it will show [USB: Download] in [Download] menu) >> PC-> HMI.
Ans. PI Series – Make Sure HMI supply is on >> open PIStudio download. Exe directly >> Connect downloading cable (If HMI is accessed, it will show [USB: Download] in [Download] menu) >> Enter Password (If uploading Password set) >> HMI-> PC.
Decompile uploaded program
Open PIStudio >> Project >> Decompile >> Browse .wmt file >> Enter Project password (If uploading Password set) >> Decompile.
LEVI Series- Make Sure HMI supply is on >> open download. Exe directly >>>> Connect downloading cable (If HMI is accessed, it will show [USB: Download] in [Download] menu) >> Enter Password (If uploading Password set) >> HMI-> PC
Decompile uploaded program
Open LEVIStudioU >> Tool >> Decompile >> Browse .hmt (General Series) or .ehmt (2000 Series) file >> Project password (If uploading Password set) >> Decompile.
Ans. PI Series- Open PIStudio >> Project Setting >> Designer Password >> ok.
LEVI Series- Open LEVIStudioU >> Setting >> Project Properties >> Screen Security >> Designer Password.
Ans. PI Series- Open HMI Program >> Project >> Udisk Download >> Browse path of USB-disk. On HMI Press top right corner for 5 to 10 sec >> System Screen >> Update project.
LEVI Series- Open HMI Program >> Tool >> Udisk Download >> Browse path of USB-disk. On HMI Press top right corner for 5 to 10 sec >> System Screen >> Update project.
Ans. PI Series- Open PIStudio Download (If HMI is accessed, it will show [USB: Download] in [Download] menu) >> Sync HMI clock with PC.
LEVI Series- Open Download (If HMI is accessed, it will show [USB: Download] in [Download] menu) >> Sync HMI clock with PC.